Latest CDCP Dumps Book - Exam CDCP Discount
Latest CDCP Dumps Book - Exam CDCP Discount
Blog Article
Tags: Latest CDCP Dumps Book, Exam CDCP Discount, Practice CDCP Tests, CDCP Reliable Cram Materials, CDCP New Dumps Ebook
What's more, part of that NewPassLeader CDCP dumps now are free: https://drive.google.com/open?id=1UEGV3uPOKLUak_iVFtPFJYgAUzpa1bIF
CDCPcertification exam questions have very high quality services in addition to their high quality and efficiency. If you use CDCPtest prep, you will have a very enjoyable experience while improving your ability. We have always advocated customer first. If you use our CDCP Learning Materials to achieve your goals, we will be honored. And our CDCP pdf files give you more efficient learning efficiency and allows you to achieve the best results in a limited time. Our CDCP pdf files are the best exam tool that you have to choose.
EXIN CDCP Exam Syllabus Topics:
Topic | Details |
---|---|
Topic 1 |
|
Topic 2 |
|
Topic 3 |
|
Topic 4 |
|
Topic 5 |
|
Topic 6 |
|
Topic 7 |
|
Topic 8 |
|
Exam Questions for the EXIN CDCP Exam 2025 - Pass Easily
Different person has different goals, but our NewPassLeader aims to help you successfully pass CDCP exam. Maybe to pass CDCP exam is the first step for you to have a better career in IT industry, but for our NewPassLeader, it is the entire meaning for us to develop CDCP exam software. So we try our best to extend our dumps, and our NewPassLeader elite comprehensively analyze the dumps so that you are easy to use it. Besides, we provide one-year free update service to guarantee that the CDCP Exam Materials you are using are the latest.
EXIN Certified Data Centre Professional (CDCP) Sample Questions (Q24-Q29):
NEW QUESTION # 24
When dealing with glass door racks, cool air is injected into the rack from:
- A. The bottom of the rack.
- B. The front door in a downflow direction.
- C. The rear door in a downflow direction.
- D. The top of the rack through the fans and vents mounted inside the rack.
Answer: C
Explanation:
Glass door racks are a type of rack that have solid glass front doors and rear door heat exchangers (RDHx).
RDHx are devices that use facility coolant to absorb heat from the exhaust air of the IT equipment and return cool air to the room. RDHx can be either passive or active, depending on the fan configuration. In general, IT hardware within the rack is air-cooled and the door heat exchanger uses facility coolant to absorb heat from exhaust air to return air to the facility at or near inlet air temperature to the rack. This rear door heat exchanger can either be a passive or active solution. When dealing with glass door racks, cool air is injected into the rack from the rear door in a downflow direction. This means that the cool air flows from the top to the bottom of the rack, following the natural convection of the hot air rising. This way, the cool air can reach all the IT equipment in the rack and prevent hot spots or overheating.
References: [SOLVED] Rack - Solid or Mesh front door? - Data Center
IT](https://community.spiceworks.com/topic/510677-rack-solid-or-mesh-front-door), ChilledDoor, Rear Door Heat Exchanger | Data Center Cooling, ACS Door Heat Exchanger Requirements for Open Rack.
NEW QUESTION # 25
How many monitoring points should be used in Temperature Measurement?
- A. 0
- B. 1
- C. 2
- D. 3
Answer: A
Explanation:
According to the EPI Data Centre Professional (CDCP®) Reference Materials, the recommended number of monitoring points for temperature measurement in a data centre is 3 per rack: one at the top, one at the middle, and one at the bottom1. This is to ensure that the temperature distribution within the rack is uniform and within the acceptable range for the equipment. The temperature sensors should be placed at the front of the rack, where the air enters the equipment, and not at the back, where the hot air exits1.
References: 1: EPI Data Centre Professional (CDCP®) Reference Materials, page 23.
NEW QUESTION # 26
Which is the most damaging type of floor load?
- A. Rolling Load (RL)
- B. Uniformly Distributed Load (UDL)
- C. Concentrated Load / Point Load (CP/ PL)
- D. All loads are equally damaging to raised floor tiles
Answer: A
Explanation:
The most damaging type of floor load for raised floor tiles in a data centre is the rolling load (RL), according to the CDCP Preparation Guide1 and various web sources234. A rolling load is the load that is applied by a moving object, such as a pallet jack, a forklift, or a rack on wheels. A rolling load can cause more stress and fatigue on the raised floor tiles than a static load, such as a concentrated load (CP) or a uniformly distributed load (UDL), because it creates dynamic forces and impacts that can crack, dent, or deform the tiles. Moreover, a rolling load can also damage the pedestals and stringers that support the tiles, and cause the tiles to become loose or misaligned. Therefore, when designing and installing a raised floor system, it is important to consider the maximum rolling load that the tiles can withstand, and to use appropriate materials and methods to enhance the strength and durability of the tiles. For example, some possible solutions include using steel or concrete-filled tiles, reinforcing the edges and corners of the tiles, and using locking or gravity-held systems to secure the tiles.
References:
1: CDCP Preparation Guide, page 23, section 2.4.2 2: Top 5 Considerations - Selecting a Data Center Raised Floor Tile5, page 1, section 1 3: Raised Floor Systems: Explained, Improved and Reinvented6, page 1, section
1 4: Raised Floor Systems: Common Problems and Solutions7, page 1, section 1
NEW QUESTION # 27
Sprinkler heads used in computer rooms activate at what temperature?
- A. Only on direct contact with a flame
- B. 70 C (158 °F)
- C. 57 °C (135 °F)
- D. 27 °C (81 °F)
Answer: C
Explanation:
Sprinkler heads used in computer rooms activate at 57 °C (135 °F), which is the standard temperature rating for ordinary sprinklers. This is the temperature at which the heat-sensitive element of the sprinkler head, such as a glass bulb or a fusible link, breaks or melts, allowing water to flow from the sprinkler. Sprinkler heads are designed to activate only when exposed to a fire, not to ambient temperature fluctuations. Therefore, sprinkler heads should be installed at a sufficient distance from the heat sources, such as servers, racks, or ducts, to avoid accidental activation. Sprinkler heads should also be selected and installed in accordance with the relevant standards and codes, such as NFPA 13 and NFPA 75.
References:
1: CDCP Preparation Guide, page 24, section 2.4.3 2: Sprinkler Systems in Data Centers3, page 1, section 1 4:
Data Center Fire Protection5, page 1, section 2 6: Data Center Sprinkler System Design7, page 1, section 1
NEW QUESTION # 28
What is the most preferred unit of measure for cooling capacity?
- A. Watt
- B. Horsepower
- C. BTU
- D. Ton
Answer: A
Explanation:
Cooling capacity is the measure of a cooling system's ability to remove heat from a space. The most preferred unit of measure for cooling capacity is watt (W), which is the SI unit for power. Watt is defined as the amount of energy transferred or converted per unit time. One watt is equal to one joule of energy per second. Using watt as the unit of measure for cooling capacity allows for easy comparison and calculation of the cooling performance and efficiency of different cooling systems.
Other units of measure for cooling capacity are ton, BTU, and horsepower, but they are less common and less convenient than watt. Ton is a unit of measure that describes how much water at freezing temperature can be frozen in 24 hours, equivalent to 3.5 kW or 12,000 BTU/h. BTU (British Thermal Unit) is a unit of measure that describes the amount of heat required to raise the temperature of one pound of water by one degree Fahrenheit, equivalent to 0.293 W. Horsepower is a unit of measure that describes the rate at which work is done, equivalent to 746 W.
References:
*Data Centre Professional (CDCP®) Reference Materials, page 8, section 2.1.1
*Data Centre Professional (CDCP®) Preparation Guide, page 11, section 2.1.1
*Cooling capacity - Wikipedia
*Air Conditioner BTU Calculator
*Air conditioning 101: Basics, working principle and sizing ... - GlobalSpec
*How is cooling capacity measured? - Sage-Advices
*Everything You Need to Know About Cooling Capacity
NEW QUESTION # 29
......
These Certified Data Centre Professional (CDCP) (CDCP) certification exam's benefits assist the CDCP exam dumps to achieve their career objectives. To do this you just need to pass the CDCP exam which is quite challenging and demands complete CDCP exam questions preparation. For the quick and complete EXIN CDCP PDF Questions preparation you can get help from NewPassLeader. The NewPassLeader is a leading platform that offers valid, updated, and real CDCP Questions that are particularly designed for quick and complete CDCP exam preparation.
Exam CDCP Discount: https://www.newpassleader.com/EXIN/CDCP-exam-preparation-materials.html
- Providing You Marvelous Latest CDCP Dumps Book with 100% Passing Guarantee ???? Copy URL ➠ www.actual4labs.com ???? open and search for ➥ CDCP ???? to download for free ⛑Test CDCP Book
- CDCP Instant Access ???? CDCP Test Answers ???? Valuable CDCP Feedback ???? Search for [ CDCP ] and download exam materials for free through ➥ www.pdfvce.com ???? ????Valid CDCP Exam Duration
- CDCP Training Materials ???? CDCP Training Materials ???? Valuable CDCP Feedback ???? Search for 【 CDCP 】 and download exam materials for free through ⏩ www.examcollectionpass.com ⏪ ????Valuable CDCP Feedback
- Providing You Marvelous Latest CDCP Dumps Book with 100% Passing Guarantee ???? Search for ➤ CDCP ⮘ and easily obtain a free download on ➥ www.pdfvce.com ???? ????Valuable CDCP Feedback
- Valid CDCP Exam Duration ???? CDCP Practice Guide ???? Exam CDCP Questions Pdf ???? Search for ( CDCP ) and download it for free immediately on 《 www.prep4pass.com 》 ????CDCP Certification
- New CDCP Dumps Sheet ???? Valid CDCP Exam Duration ???? Exam CDCP Questions Pdf ???? Enter ➡ www.pdfvce.com ️⬅️ and search for ▷ CDCP ◁ to download for free ????CDCP Latest Exam Dumps
- CDCP - Certified Data Centre Professional (CDCP) Perfect Latest Dumps Book ✈ Open 《 www.pdfdumps.com 》 enter { CDCP } and obtain a free download ????CDCP PDF Question
- CDCP Instant Access ???? CDCP Certification ???? CDCP PDF Question ???? Download { CDCP } for free by simply searching on ⇛ www.pdfvce.com ⇚ ????CDCP Official Cert Guide
- Certified CDCP Questions ⏮ New CDCP Mock Exam ???? Valid CDCP Exam Duration ???? Open 【 www.examdiscuss.com 】 and search for ➤ CDCP ⮘ to download exam materials for free ????New CDCP Mock Exam
- Pass Guaranteed Quiz 2025 EXIN Reliable CDCP: Latest Certified Data Centre Professional (CDCP) Dumps Book ???? Search for 【 CDCP 】 on ➡ www.pdfvce.com ️⬅️ immediately to obtain a free download ????CDCP Practice Guide
- Exam CDCP Questions Pdf ???? New CDCP Exam Name ???? Certified CDCP Questions ???? Copy URL ➠ www.passcollection.com ???? open and search for ▛ CDCP ▟ to download for free ????New CDCP Dumps Sheet
- CDCP Exam Questions
- lms.myskillworld.in iddrtech.com shikhboanayase.com www.goodgua.com learn.degree2destiny.com bracesprocoach.com jiyangtt.com sivagangaisirpi.in tejadigiscore.online studentguidelines.com
BTW, DOWNLOAD part of NewPassLeader CDCP dumps from Cloud Storage: https://drive.google.com/open?id=1UEGV3uPOKLUak_iVFtPFJYgAUzpa1bIF